Station Post Insulators – 84-123kV
MN 84.10.2.870
MN 123.4.2.3180
MN 123.6.4.1220
MN 123.6.4.1220 PCD 200
Catalog Drawing No. |
Type |
Section Length |
Creepage Distance |
Un |
Power-Frequency Whitstand Voltage Wet |
Power-Frequency Whitstand Voltage Dry |
Lighting Impulse Whitstand Voltage |
SML |
Minimum Failing Load Bending |
Minimum Failing Load Torsion |
Approx. Weight |
Standards |
- |
- |
mm |
mm |
kV |
kV |
kV |
kV |
kN |
kN |
kN.m |
kg |
IEC, BDS, EN |
0076 |
MN 84.10.2.870 |
870 |
2180 |
84 |
140 |
- |
380 |
- |
10 |
2 |
15.000 |
61109 61952 |
0030 |
MN 123.4.2.3180 |
1220 |
3180 |
123 |
350 |
450 |
550 |
- |
4 |
2 |
17.000 |
61109 61952 |
0078 |
MN 123.6.4.1220 |
1500 |
3115 |
110 |
350 |
- |
550 |
- |
6 |
4 |
21.500 |
61109 61952 |
0078200 |
MN 123.6.4.1220 PCD 200 |
1220 |
3100 |
110 |
350 |
- |
550 |
- |
6 |
4 |
21.500 |
61109 61952 |